Partial Discharge (PD) in Resin-Cast Dry-Type Transformers: Causes, Hazards, and Detection Methods

Oct 16, 2026

Leave a message

b1321c612ea7e59088adbeb58ffe10e6

Partial discharge (PD) is the most common and insidious potential fault in resin-cast dry-type transformers. It is a primary driver of insulation aging and breakdown, often leading to the total failure of the equipment. Since many early-stage faults in dry-type transformers originate from minor partial discharges, understanding their causes, associated risks, and detection techniques is essential for ensuring stable equipment operation.
The root causes of partial discharge generally fall into three categories. First, there are defects in the manufacturing process: during the resin-casting of windings, inadequate resin impregnation can leave behind air bubbles, impurities, or voids. Once the equipment is energized, the electric field concentrates at these bubble sites, triggering partial discharge. Second, issues during on-site installation-such as residual dust, misaligned wiring, or insufficient insulation clearance-can cause local electric field distortion. Third, long-term operational aging-exacerbated by prolonged exposure to high temperatures, moisture, or overloads-can cause the resin insulation to age, crack, and develop microscopic discharge channels.
The hazards posed by partial discharge are both progressive and destructive. In the early stages, minor partial discharge produces no obvious abnormal noise or temperature rise, making it difficult to detect during routine manual inspections. However, persistent, long-term discharge gradually erodes the resin insulation, leading to carbonization, cracking, and delamination, while the area affected by the discharge continues to expand. As the fault intensifies, the equipment may begin to emit abnormal sounds, experience excessive temperature rises, and show a decline in insulation resistance. Ultimately, this can result in winding short circuits or insulation breakdown, causing equipment downtime, burnout, or even serious safety incidents.
Currently, the industry primarily employs two types of detection: offline testing and online monitoring. Offline testing is a standard procedure conducted before commissioning or during scheduled maintenance. It involves using a partial discharge detector to apply the rated voltage to the transformer windings, measuring the magnitude of any discharge to assess the condition of the insulation. This process is a mandatory step for both factory acceptance testing and on-site commissioning. Online monitoring is applicable to critical equipment in data centers, underground substations, and key industrial or commercial power distribution systems. By installing partial discharge (PD) sensors, the system collects PD data in real time, 24 hours a day. This enables early warnings of abnormal discharge, allowing for the proactive identification of potential faults and helping to prevent unexpected downtime.
To fundamentally avoid issues related to partial discharge, it is essential to maintain strict control over the manufacturing process-ensuring that resin vacuum casting is free from bubbles and impurities. Furthermore, adhering to proper on-site installation standards and conducting regular maintenance and inspections-such as checking for insulation aging, moisture ingress, or dust accumulation-can significantly extend the service life of dry-type transformers.

 

 