Product Overview
The 10 kV distribution transformer is a three-phase oil-immersed unit for stepping 10 kV down to 0.4 kV. It is used in industrial plants, commercial buildings, residential networks and small utility substations. Standard capacity options run from 30 to 1,600 kVA.
The page lists a 10 kV primary as standard. If the local network is described as 11 kV, confirm the nominal system voltage, insulation level and tap range before selection. A transformer labelled 10 kV should not be ordered for an 11 kV network without checking the project design.
Send the kVA, primary and secondary voltage, frequency, vector group, tap range, installation location and destination port for quotation.
How to select a 10 kV transformer
Start with the nominal system voltage and the required secondary voltage. Then confirm the load calculation, future expansion, impedance, losses, cooling method and installation environment. For outdoor use, the enclosure, oil containment and clearance requirements also affect the design.
Product Advantages
• Available from 30 to 1,600 kVA for distribution projects.
• ONAN cooling is standard; ONAF designs can be reviewed against the load and site conditions.
• Copper or aluminium windings are selected for the load profile, loss requirement and commercial budget.
• The sealed corrugated tank limits oil contact with moisture and airborne contamination.
• Routine test reports and nameplate data are checked with the shipment documents.




Technical Specifications
|
Parameter |
Project |
Typical values / range |
|
Basic parameters |
Rated voltage (high voltage side) |
10kV |
|
Rated voltage (low voltage side) |
0.4kV |
|
|
Rated frequency |
50Hz / 60Hz |
|
|
Number of phases |
Three-phase |
|
|
Rated capacity (kVA) |
30, 50, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600 (custom sizes available upon request) |
|
|
Cooling method |
ONAN (self-cooled), ONAF (air-cooled) |
|
|
Connection and tap |
Connection Group |
Dyn11,Yyn0 |
|
Tap method |
No-load voltage regulation / On-load voltage regulation (customized) |
|
|
Tap range |
±2×2.5%,±4×2.5% |
|
|
Impedance and loss |
short-circuit impedance |
4%–6% (customized according to capacity and system requirements) |
|
Applicable Standards |
GB 1094,GB/T 6451,IEC 60076,ANSI,IEEE,JIS |
|
|
Environment and Protection |
insulating oil |
25# and 45# transformer oil |
|
Operating ambient temperature |
-30℃~+45℃ |
|
|
altitude |
≤1000m (High-altitude version available upon request) |
|
|
Temperature rise limit |
Oil top temperature rise ≤55K, average winding temperature rise ≤65K |
Product Features
|
Selection point |
What to confirm |
|
System voltage |
Confirm whether the network is nominal 10 kV or 11 kV, including insulation level and tap range. |
|
Capacity |
Start from calculated maximum demand, power factor, future load and allowable loading. |
|
Secondary voltage |
Confirm 0.38 or 0.4 kV and the outgoing cable or busbar arrangement. |
|
Installation |
For outdoor installation, confirm clearance, oil containment, earthing and fire requirements for the site. |



Frequently asked questions
What is the difference between a 10 kV and 11 kV transformer?
The difference starts with the nominal system voltage and insulation design. A 10 kV transformer is not automatically suitable for an 11 kV network. Send the network voltage, frequency, existing equipment rating and single-line diagram so the design can be checked before quotation.
Can a 10 kV transformer be installed outdoors?
Yes, oil-immersed units are commonly used outdoors when the installation meets the project clearances, oil-containment, earthing and fire requirements. The final arrangement depends on local rules and the site layout.
Which capacity should I choose?
Use the calculated maximum demand, power factor, future load and allowable loading. Do not select from kVA alone when the load profile or expansion plan is not yet known.
Project quotation: Send the 10 kV network details, kVA, frequency and destination to sales@unionpowertransformer.com or WhatsApp +86 130 2771 5769.
Product Information and Certificates
We provide the following complete technical documentation and quality documents:
• Material Safety Data Sheet (MSDS)
• Factory Test Report
• Certificate of Conformity
• Product Certificate
• Product Installation and Operation Manual
Hot Tags: 10 kV transformer, 10kV transformer, 10 kV Distribution Transformer, 10kV distribution transformer, 11 kV transformer, aluminum winding power transformer, cast coil power transformer, compact power transformer, dry type power transformer, low loss power transformer, step up power transformer