10 kV Distribution Transformer

10 kV Distribution Transformer
Details:
10 kV oil-immersed distribution transformer for stepping 10 kV down to 0.38 or 0.4 kV in industrial, commercial, residential and small utility projects. Send the kVA, voltage ratio, frequency and destination for a project quotation.
Send Inquiry
Description
Send Inquiry

Product Overview

 

The 10 kV distribution transformer is a three-phase oil-immersed unit for stepping 10 kV down to 0.4 kV. It is used in industrial plants, commercial buildings, residential networks and small utility substations. Standard capacity options run from 30 to 1,600 kVA.

 

The page lists a 10 kV primary as standard. If the local network is described as 11 kV, confirm the nominal system voltage, insulation level and tap range before selection. A transformer labelled 10 kV should not be ordered for an 11 kV network without checking the project design.

 

Send the kVA, primary and secondary voltage, frequency, vector group, tap range, installation location and destination port for quotation.

 

How to select a 10 kV transformer

 

Start with the nominal system voltage and the required secondary voltage. Then confirm the load calculation, future expansion, impedance, losses, cooling method and installation environment. For outdoor use, the enclosure, oil containment and clearance requirements also affect the design.

 

Product Advantages

 

• Available from 30 to 1,600 kVA for distribution projects.

• ONAN cooling is standard; ONAF designs can be reviewed against the load and site conditions.

• Copper or aluminium windings are selected for the load profile, loss requirement and commercial budget.

• The sealed corrugated tank limits oil contact with moisture and airborne contamination.

• Routine test reports and nameplate data are checked with the shipment documents.

Power Transformer 02
Power Transformer 03
Power Transformer 04
Power Transformer 05

 

Technical Specifications

 

Parameter

Project

Typical values ​​/ range

Basic parameters

Rated voltage (high voltage side)

10kV

Rated voltage (low voltage side)

0.4kV

Rated frequency

50Hz / 60Hz

Number of phases

Three-phase

Rated capacity (kVA)

30, 50, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600 (custom sizes available upon request)

Cooling method

ONAN (self-cooled), ONAF (air-cooled)

Connection and tap

Connection Group

Dyn11,Yyn0

Tap method

No-load voltage regulation / On-load voltage regulation (customized)

Tap range

±2×2.5%,±4×2.5%

Impedance and loss

short-circuit impedance

4%–6% (customized according to capacity and system requirements)

Applicable Standards

GB 1094,GB/T 6451,IEC 60076,ANSI,IEEE,JIS

Environment and Protection

insulating oil

25# and 45# transformer oil

Operating ambient temperature

-30℃~+45℃

altitude

≤1000m (High-altitude version available upon request)

Temperature rise limit

Oil top temperature rise ≤55K, average winding temperature rise ≤65K

 

Product Features

 

Selection point

What to confirm

System voltage

Confirm whether the network is nominal 10 kV or 11 kV, including insulation level and tap range.

Capacity

Start from calculated maximum demand, power factor, future load and allowable loading.

Secondary voltage

Confirm 0.38 or 0.4 kV and the outgoing cable or busbar arrangement.

Installation

For outdoor installation, confirm clearance, oil containment, earthing and fire requirements for the site.

 

product-800-892

product-800-782

product-800-809

 

Frequently asked questions

 

What is the difference between a 10 kV and 11 kV transformer?

The difference starts with the nominal system voltage and insulation design. A 10 kV transformer is not automatically suitable for an 11 kV network. Send the network voltage, frequency, existing equipment rating and single-line diagram so the design can be checked before quotation.

 

Can a 10 kV transformer be installed outdoors?

Yes, oil-immersed units are commonly used outdoors when the installation meets the project clearances, oil-containment, earthing and fire requirements. The final arrangement depends on local rules and the site layout.

 

Which capacity should I choose?

Use the calculated maximum demand, power factor, future load and allowable loading. Do not select from kVA alone when the load profile or expansion plan is not yet known.

 

Project quotation: Send the 10 kV network details, kVA, frequency and destination to sales@unionpowertransformer.com or WhatsApp +86 130 2771 5769.

 

Product Information and Certificates

 

We provide the following complete technical documentation and quality documents:

• Material Safety Data Sheet (MSDS)

• Factory Test Report

• Certificate of Conformity

• Product Certificate

• Product Installation and Operation Manual

 

Hot Tags: 10 kV transformer, 10kV transformer, 10 kV Distribution Transformer, 10kV distribution transformer, 11 kV transformer, aluminum winding power transformer, cast coil power transformer, compact power transformer, dry type power transformer, low loss power transformer, step up power transformer