How to prevent moisture from entering a dry type transformer?

Nov 19, 2026

Leave a message

Sophia Taylor
Sophia Taylor
Sophia is a marketing specialist at UPCN. She is responsible for promoting the company's products and one - stop power solutions. Through effective marketing strategies and communication skills, she has increased the company's brand awareness and attracted more global customers.

If you’ve ever dealt with transformers in industrial settings, you know moisture is the silent enemy of dry-type models. Unlike oil-filled transformers that have liquid to insulate and regulate temperature, dry-type transformers rely on air and solid insulation (usually resin, paper, or composite materials) to operate safely. Once moisture sneaks in, it wreaks havoc on insulation, reduces efficiency, causes overheating, and can even lead to catastrophic failures—especially in high-demand environments like data centers, manufacturing plants, or commercial buildings. As a supplier of dry-type transformers, I’ve seen firsthand how even small moisture-related issues can turn into big headaches for clients. Today, I’m breaking down practical, science-backed ways to keep moisture out of your dry-type transformer, no matter where it’s installed.

First, let’s get why moisture is such a big deal for these units. Dry-type transformers are rated to operate with a maximum moisture content in their insulation systems—usually around 0.5% to 1% by weight, depending on the model. When humidity (from things like outdoor rain, indoor steam, or seasonal changes) penetrates the enclosure, it gets absorbed by the insulation materials. This lowers the insulation resistance, which is the transformer’s main defense against electrical arcing. Over time, trapped moisture can also cause corrosion on internal copper windings, short circuit paths, and reduce the transformer’s lifespan by years. The good news? Most moisture issues are preventable with proper planning and regular checks.

Let’s start with the basics that many people overlook: enclosure design and installation. A dry-type transformer’s enclosure is its first line of defense, so skimping on this is a huge mistake. When I’m talking to clients about their setup, I always ask about their installation location first. If it’s outdoors, you need an enclosure rated for outdoor use—meaning it’s weatherproof, has sealed gaskets on all doors and panels, and no gaps where water can seep in. Even indoor installations can be risky if the area is prone to high humidity, like near laundry rooms, water treatment facilities, or HVAC units that leak. For example, I recently worked with a manufacturing client who installed their 125 Kva Transformer in a space right next to a parts washing station. Within six months, moisture had corroded the winding terminals, and they had to do emergency repairs. The fix was simple: move the transformer to a drier spot and upgrade the enclosure with extra moisture-sealing gaskets.

When installing, pay attention to cable entry points too. That’s another common place moisture sneaks in. When you run power cables into the transformer, the hole you cut for the cable can leave gaps—even if it’s just a small opening. Use cable glands or sealing compounds specifically made for electrical equipment to seal these gaps. Don’t just use generic caulk; it can degrade over time from heat and electrical current, leaving openings. Also, make sure the enclosure has proper drainage if it’s outdoors. No, I don’t mean a pool of water under the unit—small, sloped drains at the bottom of the enclosure keep any rain that does get in from pooling around the transformer base, which can wick moisture up into the windings.

Next up, environmental control. If your transformer is in a space with consistently high humidity, you can’t just rely on the enclosure to do all the work. That’s where climate control comes in. For indoor installations, especially in tightly controlled spaces like server rooms or data centers, using dehumidifiers is a game-changer. Aim for a relative humidity (RH) level between 30% and 50% year-round. I had a client with a 80 KVA Dry Type Power Transformer powering their office building; they didn’t have a dehumidifier, and during the rainy season, RH hit 70%. We added a small dehumidifier near the transformer’s enclosure, and within a month, their insulation resistance levels went back to normal. For outdoor installations, some high-voltage models use ventilation systems with heated air to keep the interior dry—these are called “dry air purge systems.” They pull in dry air, circulate it through the enclosure, and exhaust moist air, maintaining a constant low-humidity environment even in wet climates.

Wait, but what if your transformer is in a dusty or dirty area, like a factory floor? You might be tempted to skip ventilation to keep dust out, but that actually traps moisture along with dust. Dust can hold moisture too, creating a damp layer on the enclosure that eventually seeps in. The solution here is filtered ventilation. Use high-quality, dust-resistant filters on the enclosure’s vents, and replace them every 6 to 12 months (more often if the environment is extra dirty). The filters let in dry air while blocking dust, so you get the best of both worlds. I recently upgraded a client’s 300 Kva Dry Type Transformer in a metal stamping plant with filtered vents; they used to have to clean the enclosure every week to remove dust buildup, and now they only clean it once a month—plus, no more moisture-related alarms.

Regular maintenance is non-negotiable, but it doesn’t have to be complicated. Most people think maintenance means just checking for loose connections, but moisture checks are a key part of it. The easiest way to test for internal moisture is to measure the insulation resistance (IR) of the windings using a megohmmeter. You should do this at least once a year, and after any big weather event (like a heavy storm or flood that could have affected the enclosure). If the IR reading is lower than the manufacturer’s recommendation, that’s a sign moisture is present. Another test is the polarization index (PI), which compares the IR reading at 1 minute vs. 10 minutes. A PI below 1.5 means there’s definitely moisture in the insulation.

When you do maintenance, don’t forget to inspect the enclosure for damage. Even small scratches or dents can break the seal of the gaskets, letting moisture in over time. Check the gaskets too—are they cracked, brittle, or missing? Gaskets should be replaced every 2 to 3 years, even if they look fine, because they degrade from heat, UV rays, and age. I always tell clients to keep spare gaskets on hand, because replacing them is a 10-minute fix that prevents a lot of trouble. For resin-type dry transformers, like our 160 KVA Dry Resin Transformer, also check the resin surface for cracks. Cracks in the resin can let moisture seep directly into the windings, so if you see any, you’ll need to repair or recoat the resin as soon as possible.

Another thing people miss: temporary moisture during installation or storage. If your transformer is sitting on a job site waiting to be installed, it’s exposed to rain, humidity, and even dew, so you can’t just leave it in its shipping crate. Keep it in a dry, covered space, preferably with a small dehumidifier running inside the crate if it’s going to be stored for more than a month. Some of our clients who work on long-term projects have storage containers with dehumidifiers specifically for holding transformers—this prevents moisture buildup before the unit is even put into use.

What about emergency fixes if you suspect moisture is already inside? If the IR reading is low, you can do a “bake-out” of the windings. That means heating the transformer’s windings to around 100°C to 120°C for several hours (usually 24 to 48 hours) to evaporate the trapped moisture. You can do this by running the transformer at a low load, using external heaters, or a combination of both. But be careful—don’t overheat it, because that can damage the insulation. If you’re not comfortable doing a bake-out, hire a professional technician who has experience with dry-type transformers. And after baking, always recheck the IR and PI levels to make sure the moisture is gone.

Let’s also talk about common myths. I hear a lot of people say, “Dry-type transformers don’t need humidity control because they’re ‘dry’.” No—dry-type just means they don’t have oil, not that they can handle any amount of moisture. Another myth is that sealing the enclosure completely is the best solution. If you seal it all the way, any moisture that does get in can’t escape, so it just builds up over time. Balance is key: use sealed gaskets to keep most moisture out, but have enough ventilation to let any small amount of moisture that gets in escape before it causes damage.

Now, as a supplier, I can tell you that choosing the right transformer model for your environment goes a long way. For example, if you’re installing in a coastal area with high salt and humidity, we offer models with enhanced corrosion-resistant enclosures. If you need a unit for a large commercial building, our 2500 KVA Dry Type Transformer comes with a sealed, weatherproof enclosure and optional dry air purge systems. Even smaller units, like our 80 KVA or 125 KVA models, can be customized with extra gasket seals and filtered vents for high-humidity locations. The key is to tell your supplier about your specific environment—they can recommend the right model and upgrades to prevent moisture issues.

At the end of the day, preventing moisture in dry-type transformers is about being proactive, not reactive. Small steps—like checking enclosure seals annually, keeping humidity levels in check, and doing regular insulation tests—can save you thousands in emergency repairs and downtime. I’ve seen clients skip these steps and end up with a transformer that’s out of commission for weeks, costing them lost production or revenue. The best part? Most moisture prevention measures are simple, affordable, and easy to incorporate into your routine maintenance.

125 Kva Transformer high quality160 KVA Dry Resin Transformer high quality

If you’re looking for a reliable dry-type transformer that’s built to resist moisture, or you need help troubleshooting existing units that have moisture issues, feel free to reach out. We work with all kinds of industries, from small businesses to large industrial facilities, and we can help you pick the right model for your space, as well as share more maintenance tips to keep your transformer running smoothly for years.


References

  1. IEEE Std C57.12.01, "Standard for General Requirements for Dry-Type Distribution and Power Transformers," Institute of Electrical and Electronics Engineers, 2020.
  2. National Electrical Manufacturers Association (NEMA) Standard 250, "Enclosures for Electrical Equipment," NEMA, 2018.
  3. "Moisture Control in Dry-Type Transformers," American Society of Mechanical Engineers (ASME) Power Division Technical Paper, 2021.
  4. "Maintenance Guidelines for Dry-Type Power Transformers," Electric Power Research Institute (EPRI), 2019.